§ 45.1-161.182. Surface transformers

VA Code § 45.1-161.182 (2019) (N/A)
Copy with citation
Copy as parenthetical citation

A. Surface transformers which are not isolated by elevation of eight feet or more above the ground shall be enclosed in a transformer house or surrounded by a suitable fence at least six feet high. If the enclosure or fence is of metal, it shall be grounded effectively. The door to the enclosure or the gate to the fence shall be kept locked at all times unless persons authorized to enter the gate or enclosure are present.

B. Surface transformers containing flammable oil and installed near mine openings, in or near combustible buildings, or at other places where they present a fire hazard shall be provided with means to drain or to confine the oil in the event of rupture of the transformer casing.

Code 1950, § 45-82.2; 1954, c. 191; 1966, c. 594, § 45.1-76; 1994, c. 28.