§ 12-129. Detectable wires for connecting buildings to water supply or sewerage systems.

MD Pub Util Code § 12-129 (2019) (N/A)
Copy with citation
Copy as parenthetical citation

(a)    Subject to subsection (c) of this section, any new or replacement piping that is buried or installed for the purpose of connecting a building to a water supply system or a sewerage system shall be buried or installed with a wire that makes the piping detectable.

(b)    The wire required under subsection (a) of this section shall:

(1)    be an insulated copper tracer wire that is suitable for direct burial and has an American wire gauge (AWG) of at least 10, or an equivalent product;

(2)    be installed:

(i)    in the same trench as the piping that connects the building to the water supply system or the sewerage system;

(ii)    within 12 inches of the piping that connects the building to the water supply system or the sewerage system; and

(iii)    with at least one end of the wire terminating above grade in a location that is accessible and resistant to physical damage, such as in a cleanout or next to an external wall of the building; and

(3)    run from within 5 feet of an external wall of the building to:

(i)    the point where the piping intersects with the water supply system or the sewerage system; or

(ii)    the point where the sewerage system disposes of or processes the sewage.

(c)    The requirement of subsection (a) of this section with regard to replacement piping connecting a building to a water supply system or a sewerage system:

(1)    applies only to a complete replacement of the piping; and

(2)    does not apply to a repair or a partial replacement of the piping.